2. Wall Insulation
- Masonry Cavity Wall Insulation
Masonry walls, inclusive of collar jointed and cavity walls, shall comply with the requirements of SANS10400-K (Walls). External walls are defined as the complete walling system, as measured from the outer skin exposed to the environment, to the inside of the inner skin exposed to the interior of the building, and does not include glazing.
The Minimum total R-value requirements for an external wall with a surface density greater than 270kg/m² shall be as per below.
Minimum R-value requirements for walls with a surface density greater than and equal to 270 kg/m² | |||||||
Walls – Mandatory | Non-mandatory but sensible: with Insulation (alphabetically) |
||||||
Surface Density | Energy Zones | R-Value | Example | +50mm EPS |
+50mm MW |
+50mm PU |
+50mm XPS |
Generic R-Value of Product | |||||||
R=1.43 | R=1.52 | R=2.00 | R=1.79 | ||||
Total R-Value of Wall System (Cavity + Insulation) |
|||||||
>270kg/m2 | 1 | 0,5 | 50mm cavity wall, plastered internally | 1.93 | 2.02 | 2.5 | 2.29 |
2 | 0,5 | 50mm cavity wall, plastered internally | 1.93 | 2.02 | 2.5 | 2.29 | |
3 | 0,35 | Collar jointed wall, plastered internally | – | – | – | – | |
4 | 0,5 | 50mm cavity wall, plastered internally | 1.93 | 2.02 | 2.5 | 2.29 | |
5 | 0,35 | Collar jointed wall, plastered internally | – | – | – | – | |
5H | 0,35 | Collar jointed wall, plastered internally | – | – | – | – | |
6 | 0,5 | 50mm cavity wall, plastered internally | 1.93 | 2.02 | 2.5 | 2.29 | |
7 | 0,5 | 50mm cavity wall, plastered internally | 1.93 | 2.02 | 2.5 | 2.29 | |
Key: EPS: Expanded Polystyrene, MW: Mineral Wool, PU Polyurethane and XPS: Extruded Polystyrene. Note: R-values quoted are generic. For actual figures obtain thermal values from manufacturers. |
- Typical Construction Details of a Masonry Cavity Wall with Insulation
-
- Wall insulation in Light Steel Frame Construction
External walls with a surface density lighter than 270kg/m² shall achieve a minimum total R-value of:
- a) 2,2 m²K/W for energy zones 1, 2, 6 and 7; and
- b) 1,9 m²K/W for energy zones 3, 4, 5 and 5H.
A walling construction that has any metal sheet, metal studs, metal tracks or metal battens fixed to each other shall have a thermal break consisting of a material with an R-value of not less than 0.2 installed between the metal structural elements.
Typical Construction Details of a Fibre Cement Board External Cladding System
R – Value of basic elements of wall: 0,245 m².K/W (Note: Fire resistance to exceed 30 min.) Energy zone 1, 2, 6 and 7 3, 4 and 5 Minimum total R–value 2.2 m2.K/W 1.9 m2.K/W Indoor air film 0.12 0.12 Outdoor air film 0.03 0.03 9mm fibre cement 0.025 0.025 15mm Gypsum boards 0.07 0.07 Minimum required added R–value m2.K/W 1.96 1.66 Typical Construction Details of a Fibre Cement Board External Cladding System